l
l
l
         

> High Frequency DC to DC Battery Chargers

> PERTINENT FEATURES:

• DC input voltage (overhead line)
• Microprocessor controlled
• Programmable control parameters, thus charger can be
mconfigured to suite different input voltages and batteries
• Modular design ensuring easy installation and maintenance
• Built-in fault finding to shorten down time
• Forced air cooling, built-in protection for fan failure
• Input over-voltage protection
• Input under-voltage protection
• Input over-current protection
• Output over-current protection
• Output over-voltage protection
• Output under-voltage protection
• Over temperature protection
• Displays:
• Dual IGBT design to minimize losses
• Charger is entirely designed in-house by Battery Electric,
mmaking it possible modify the design according to the
mclient’s specific needs.


 

 

 

Click here to view complete user manual

> TECHNICAL SPECIFICATIONS

 

Minimum

Nominal

Maximum

Unit

Input Voltage

220

270

310

Volt

Output Voltage

136

160

212

Volt

Output Current

 

 

120

Ampere

1 st Rate

C/5 - 10%

C/5

C/5 + 10%

Ampere

2 nd Rate

C/10 - 10%

C/10

C/10 + 10%

Ampere

Operating temperature

 

 

 

 

Ambient

0

 

60

ºC

Heatsink

0

 

80

ºC

Inductor

0

 

100

ºC

Input current requirement

0.9 x (C/5)

 

 

Ampere


         


Copyright © 2007 Battery Electric
While every care has been taken to ensure the accuracy of the information on this site, neither Battery Electric nor its employees will accept responsibility or liability for the validity of any information obtained from this site.
Site designed and maintained by designBox
Tel: +27 (0) 82 324 2291
designbox@webmail.co.za